Home/Product systems/2.5 MW / 5.016 MWh Container BESS

High-power two-hour container BESS

2.5 MW / 5.016 MWh Container BESSThe 5.016 MWh platform configured for higher discharge power.

A 12-string LFP container with a 2.5 MW PCS stage, designed around approximately two-hour rated duty for larger industrial and grid-connected projects.

2.5 MW / 5.016 MWh Container BESS product configuration
Documented product configuration
2.5 MWRated AC output
5.016 MWhRated energy
2.01 hNominal duration
0.5CMaximum rate

Application fit

Start with the operating duty.

The 2.5 MW version uses the same twelve-string, 5.016 MWh battery platform as the 1.725 MW configuration but increases PCS power and maximum DC current. It is the higher-power choice when approximately two-hour duty better matches the load or dispatch target.

Open the RFQ input checklist
01High-power peak shavingDeliver a larger power block across a two-hour-class peak window.
02Grid and plant supportRespond to higher site demand within the approved control and warranty duty.
03Renewable smoothingAbsorb and release higher power around variable generation.
04Large C&I projectsServe central storage plants where the site supports container and MV infrastructure.

Integrated architecture

Four layers form the starting platform.

The commercial scope still needs a project responsibility matrix covering every external interface.

01

Battery strings

Twelve 314 Ah LFP strings provide 5.016 MWh at 1331.2 V nominal DC.

02

High-power DC collection

The collection system is coordinated for a documented maximum DC current of 2750 A.

03

2.5 MW PCS stage

A 690 V PCS interface supports the higher-power two-hour-class configuration.

04

Project integration

EMS, MV step-up, protection, SCADA and site infrastructure are resolved at project level.

Technical specifications

Documented configuration data.

Values are taken from the supplied manufacturer specification. Final purchase, installation and acceptance must use the approved project datasheet, drawings and test documents.

Engineering note: rated energy is not the same as guaranteed usable energy. Confirm SOC window, auxiliaries, ambient derating, ageing and operating reserve.
GroupParameterDocumented value
BatteryCell chemistry and formatLFP, 3.2 V / 314 Ah
BatteryRated energy5016 kWh
BatteryNominal DC voltage1331.2 V
BatteryDC voltage window1040-1500 V
BatteryString arrangement12P416S
PCSRated AC output2500 kW
PCSPCS AC voltage690 V
PCSMaximum DC current2750 A
PCSRated frequency50 Hz
ProjectTarget project-side interface10 kV through PCS step-up unit
SystemCharge/discharge rateUp to 0.5C
SystemBase container dimensions6500 x 2700 x 2950 mm
SystemService/interface envelope6700 x 3200 x 2950 mm
SystemApproximate weight44 t
SystemCommunicationsRS485 / CAN / Ethernet
EnvironmentAltitudeUp to 2000 m
EnvironmentEnclosureIP54; C3 corrosion protection
EnvironmentOperating temperature-20 C to 55 C
EnvironmentRelative humidity0-95%, non-condensing
ThermalCoolingIntelligent liquid cooling
SafetyFire suppressionPerfluorohexanone system

Scope boundary

Separate product from project.

A comparable quotation makes included equipment and external responsibilities explicit.

Starting equipment scope

Documented platform

  • Twelve-string 5.016 MWh LFP container
  • High-current DC collection and isolation
  • BMS and EMS control platform
  • Liquid cooling and auxiliary systems
  • Detection and fire suppression
  • Container communications and local control

Project boundary

Confirm before quotation

  • 2.5 MW PCS and transformer package
  • MV point of connection and fault level
  • Grid-code and dynamic-study requirements
  • Foundation, clearances and heavy transport
  • Operating profile, cycle count and degradation model
  • FAT, relay testing and commissioning responsibility

Buyer questions

Resolve these points before ordering.

Use the answers to narrow the design; use the final project documents to release the order.

Is this exactly a two-hour system?

The rated energy-to-power ratio is approximately 2.01 hours. Actual usable duration depends on SOC limits, auxiliary loads, efficiency, temperature, degradation allowance and reserve requirements.

Can the PCS output exceed 2.5 MW?

Do not assume overload capability from the page summary. Use the approved PCS datasheet and project duty definition for overload, reactive power and thermal limits.

Can it connect directly to a 10 kV bus?

The battery container feeds a 690 V PCS stage. The 10 kV connection requires the coordinated step-up transformer, switchgear, protection and grounding design.

Which tests should be included in FAT?

Define configuration identity, insulation, protection, BMS/PCS/EMS communication, alarms, E-stop, cooling, fire interfaces, startup, power tests, packing and document handover.

Buyer engineering guides

Check the assumptions around this configuration.

Connect the product data to measured demand, electrical design, safety evidence and quotation scope.

Compare adjacent configurations

Continue the product review.

Compare power, duration, interface and project boundary before selecting a starting platform.

Product quick RFQ

Match this configuration to the real site.

Send the country, operating target and the first project requirements. The product title and source page are attached automatically.

Directly routed to the project review inboxNo public pricing or purchase commitmentDetailed electrical data can follow by email